Measurement equipment

Magnetic field measurement device including probes adjusted to 50Hz and 60Hz, calibrated according to IEEE std 644-1994 and approved by the Ministry of the Environment (MOE).
Electric field measurement device including probes adjusted to 50Hz and 60Hz, calibrated according to IEEE std 644-1994 and approved by the Ministry of the Environment (MOE).

Measurement methods.

Measurement locations criteria:

    In open area:

  • Choose measurement locations wherever the highest magnetic field was found (according to a short term magnetic field measurement scan).
  • For power lines of all kinds choose measurement locations at the power line ground axis and at the nearest populated area to the power line including the nearest entrance to a populated building.
  • Choose other measurement locations as follows:
For low power lines, choose locations following a grid of 1m from the power line ground axis on both sides.
For medium power lines, choose locations following a grid of 2m from the power line ground axis on both sides.
For high and extra high power lines, choose locations following a grid of 5 m from the power line ground axis on both sides.
For sub stations and switching stations, choose locations following a grid of 1 m from the fence around the station and at the exit and entrance of the power lines cable.
For compact transformer stations, distribution cabinets and other electricity cabinets, choose locations following a grid of 0.5 m around the power source.
    
    In buildings:

  • Choose measurement locations wherever the highest magnetic field is found (according to a short magnetic field measurement scan).
  • In populated rooms, choose locations at room center and at any continuously populated areas (e.g., work desks, beds).
  • To characterize magnetic fields from external ELF sources, choose locations where the influence from other indoor ELF source (such as home appliances) will be minimal.
  • For power lines of all kinds, choose measurement locations closest to the power line direction in the building/room.
  • For indoor transformers rooms, distribution cabinets and other electricity cabinets in buildings, choose locations following a grid of 0.5 m around the power source including above and under transformer rooms if possible